33KV DISTRIBUTION TRANSFORMER Technical Data Schedule FOR 25KVA |
|||
Description |
Unit |
TANESCO |
Bid |
It complies with International standard |
|
IEC 76 |
IEC 76 |
Manufacturer |
|
|
Guangdong Guangte Electric Co.,Ltd |
Country of origin |
|
|
China |
Nominal frequency |
Hz |
50 |
50 |
Nominal power rating |
kVA |
25 |
25 |
Maximum continuous power rating |
kVA |
25 |
25 |
Nominal primary voltage |
kV |
33/11 |
33/11 |
Nominal secondary voltage |
kV |
0.4 |
0.4 |
Type of Cooling |
|
ONAN |
ONAN |
Winding Polarity/Vector Group |
|
Dyn11 |
Dyn11 |
Number of Tap Positions |
|
5 |
5 |
Percentage Regulation per Tap |
% |
2.5 |
2.5 |
Basic Impulse Level 33/11 kV |
kV |
170/75 |
170/75 |
Impedance |
% |
4 |
4 |
Short Circuit Current |
kA |
25 at full load |
25 at full load |
Short Circuit Duration |
Sec |
2 |
2 |
X/R Ratio |
|
Specify |
IEC76-5 |
Duration of Overload: 25 % |
Min. |
60 |
60 |
50% |
Min. |
1 |
1 |
Design continuous ambient temperature |
°C |
40 |
40 |
Average winding temperature rise |
°C |
55 |
55 |
Top oil temperature rise |
°C |
50 |
50 |
Maximum hot spot temperature |
°C |
98 |
98 |
Temperature Gradient |
°C |
/ |
/ |
Flux Density |
T |
1.65 |
1.65 |
RIV level at 1Mhz |
µV |
|
250000 |
Core losses |
kW |
|
0.17/0.13 |
Winding losses |
kW |
|
1/0.6 |
No load current (at full voltage) |
A |
|
2.1 |
Regulation at full load: PF=1 |
% |
|
98.78/98.98 |
PF=0.85 |
% |
|
99.21/99.35 |
Silicone Steel: Manufacturer/country of origin/Type/Grade |
% |
|
Wuhan Steel Group/China/30Q120 |
Conductor for HV Windings: Manufacturer/country of origin/Type/Grade |
|
|
Luoyang Copper Co., Ltd /China/T2 |
Conductor of LV Windings: Manufacturer/country of origin/Type/Grade |
|
|
Luoyang Copper Co., Ltd /China/T2 |
Conductor Material: |
|
|
|
HV Windings |
|
|
Cooper |
LV Winding |
|
|
Cooper |
Conductor Shape: |
|
|
|
HV Windings |
|
|
Round |
LV Winding |
|
|
Round |
Maximum current density: |
|
|
|
Copper |
A/sq.mm |
|
3.8 |
Aluminium |
A/sq.mm |
|
2.2 |
HV Bushings: Manufacturer/country of origin/Type/Grade |
|
|
Yachen/China/BLQ-35/315/ Yachen/China/BLQ-12/315 |
LV Bushings: Manufacturer/country of origin/Type/Grade |
|
|
Yachen/China/BF-1/315 |
Bushing Catalogue Number: |
|
|
|
HV |
|
|
50261/50250 |
LV |
|
|
50200 |
Bushing Basic Impulse Level: |
|
|
|
HV |
kV |
|
170/50 |
LV |
kV |
|
/ |
Bushing Power Frequency Withstand: |
|
|
|
HV |
kV |
|
70/28 |
LV |
kV |
|
3 |
Puncture Voltage of HV Bushings |
kV |
|
|
Creepage Distance: |
|
|
|
HV Bushings 33/11kV |
mm |
|
1080/360 |
LV Bushings |
mm |
|
/ |
Are arcing horns fitted? (y/n) |
|
|
Yes |
Are arcing horns adjustable? (y/n) |
|
|
Yes |
Spark gap 33/11 |
mm |
|
100-250/25-80 |
Impulse flashover level with arcing horns fitted |
kV |
|
170/70 |
Slope of upper surface of bushing shed |
|
|
/ |
Can bushings be de-tanked without detaching cover? (y/n) |
|
|
N |
Colour of bushing porcelain |
|
|
Brown |
Type of HV Terminal |
|
|
Stud |
Metal used for terminal |
|
|
Cooper |
Stud Diameter |
mm |
|
12 |
Are conic spring washers fitted? (y/n) |
|
|
Y |
Range of permissible conductor sizes |
sq.mm |
|
3.8 |
Minimum phase to phase clearance |
mm |
|
380/240 |
Minimum phase to earth clearance |
mm |
|
/ |
Bushing to arrester clearance |
mm |
|
120 |
Type of HV Terminal |
|
|
Stud |
Type of LV Terminal |
|
|
Stud |
Metal used for terminal |
|
|
Cooper |
Stud Diameter |
mm |
|
12 |
Range of permissible conductor sizes |
sq. mm |
|
/ |
Type of atmospheric protection |
|
|
Tinned |
Minimum phase to phase clearance |
mm |
|
380240 |
Minimum phase to earth clearance |
mm |
|
/ |
Continuous current rating |
A |
|
300 |
Type of earth terminal |
|
|
Stud |
Spring and lock washers included? (y/n) |
|
|
Yes |
Tap Changer: Manufacturer/Country of origin/ Type/Grade |
|
|
Zhejiang, China, T 50/35 |
Can tap changer switch be locked? (y/n) |
|
|
Yes |
Circuit breaker : Manufacturer/country of origin |
|
|
/ |
Catalogue number |
|
|
/ |
International standard it complies with |
|
|
/ |
Rated Voltage 33/11 |
kV |
|
/ |
Rated Current |
A |
|
/ |
Symmetrical Breaking Capacity |
kA rms |
|
/ |
Rated Marking Current |
kA prak |
|
/ |
Degree of Washer Protection |
|
|
/ |
Dimensions: Length |
mm |
|
/ |
Width |
mm |
|
/ |
Height |
mm |
|
/ |
Weight in service |
kg |
|
/ |
Transformer Oil: Manufacturer/ Country of origin/ Type/Grade |
|
|
Sinopec/China/25# |
Quantity of Oil |
L |
|
80/60 |
Tank Construction |
|
Hermetically Sealed |
Hermetically Sealed |
Type of Steel |
|
Mild Steel |
Mild Steel |
Grade of Steel |
|
Mild Steel |
Mild Steel |
Shape of Tank |
|
|
Rectangular |
Minimum thickness of: Tank Steel: |
mm |
3 |
4 |
Top Cover: |
mm |
|
6 |
Cooling Surfaces: |
mm |
|
1.2 |
Grade of stainless steel weldwire (if applicable) |
|
|
/ |
Is tank fully filled with oil? (y/n) |
|
|
Y |
Top oil temperature for 100kN/sq.mm |
°C |
|
60 |
Steady load to give top oil temperature (30°C ambient) |
kW |
|
1.17/0.73 |
Steady load to give top oil temperature (30°C ambient and solar radiation of 120w/sq.m) |
kW |
|
/ |
Type of cooling surfaces |
|
|
Corrugated |
Type of metal on earth terminal |
|
|
Cooper |
Is pressure relief device offered? (y/n) |
|
|
Y |
Relief pressure for relief device |
kPA/sq.mm |
|
25 |
If no pressure relief device offered how will tank behave under overpressure? |
|
|
/ |
Are transformers tested for leakage? (y/n) |
|
|
Y |
Corrosion protection |
|
|
Yes |
Galvanizing: Type/Grade |
|
Hot dip Galvanised |
Hot dip Galvanised |
Galvanizer |
|
|
/ |
Core Type |
|
|
Wounded core type |
Tank Dimensions: |
|
|
|
Width |
mm |
|
700/500 |
Depth |
mm |
|
1000/880 |
Height |
mm |
|
1450/1000 |
Diameter |
mm |
|
/ |
Can transformers be handled by forklift? (y/n) |
|
Yes |
Yes |
Weight of tank |
kg |
|
80/60 |
Weight of core and windings |
kg |
|
200/130 |
Weight of oil at 20°C |
kg |
|
180/100 |
Total weight of transformer ready for service |
kg |
|
550/300 |
Shipping weight of transformer |
kg |
|
580/330 |
Guarantee period |
Months |
|
12 |